| 1 | Universal Type 2, 3P+N, 230/400 V | TN-S, TN-C-S, TT; 230/400 V AC; 50/60 Hz | Type 2; thermally protected MOV modules | 275 V L-N; 440 V N-PE | 20 kA | 40 kA | ≤ 1.5 kV | 25 kA to 50 kA, depending on upstream backup protection | Main distribution board or sub-distribution board; DIN rail | Use short, straight conductors. Coordinate with upstream Type 1 or Type 1+2 protection where lightning exposure is high. | IEC 61643-11; IEC 60364-5-534; applicable national wiring rules | Check status indicator, protective fuse or circuit breaker, and PE bonding continuity; do not use a megohmmeter through the connected SPD. | Every 6–12 months |
| 2 | High-Exposure Type 1+2, 3P+N, 230/400 V | TN-S, TN-C-S, TT; service entrance applications | Combined Type 1+2; spark-gap or hybrid technology | 275 V L-N; 440 V N-PE | 12.5 kA per pole, 10/350 µs for Type 1 path | 50 kA, 8/20 µs for Type 2 path | ≤ 2.0 kV | 25 kA to 50 kA, subject to the installation prospective short-circuit current | Origin of installation or main switchboard | Required where an external lightning protection system or overhead supply creates direct-lightning-current risk. Follow the manufacturer’s backup-device table. | IEC 61643-11; IEC 62305; IEC 60364-5-534 | Inspect remote contacts, thermal indicators, enclosure condition, and conductor torque after a major storm or known surge. | Every 6 months |
| 3 | Industrial Type 2, 3P+N, 400/690 V | Three-phase industrial networks; 400/690 V AC | Type 2; high-energy MOV assembly | 440 V L-N or 690 V L-L, according to connection | 20 kA | 40 kA | ≤ 2.5 kV | 25 kA minimum, verified against the panel fault level | Industrial main or machine distribution panel | Install after the main disconnect and before sensitive variable-speed drives. Maintain separation from control and communication wiring. | IEC 61643-11; IEC 60204-1 where installed in machinery | Verify visual status, protective-device condition, enclosure temperature, and terminal tightness during planned shutdowns. | Every 6–12 months |
| 4 | North American 480Y/277 V, 3P+N | 480Y/277 V AC; grounded wye systems; 60 Hz | Type 1 or Type 2 service and distribution SPD | 320 V L-N; selected for 277 V phase-to-neutral service | 20 kA | 40 kA | ≤ 1.8 kV | 10 kA to 100 kA SCCR, depending on the listed protective assembly | Service equipment, switchboard, or panelboard | Confirm the SPD voltage rating matches 480Y/277 V. Do not apply a 230/400 V module to a 480Y/277 V system. | UL 1449; IEEE C62.41.1; IEEE C62.41.2; local electrical code | Use the integral status display or dry-contact alarm. Confirm that the disconnect has not operated and inspect phase indicators. | Every 6–12 months |
| 5 | North American 600Y/347 V, 3P+N | 600Y/347 V AC; grounded wye systems; 60 Hz | Type 1 or Type 2 panel-mounted SPD | 385 V L-N; selected for 347 V phase-to-neutral service | 20 kA | 40 kA | ≤ 2.0 kV | 10 kA to 100 kA SCCR, depending on the certified assembly | Service entrance, switchboard, or large distribution panel | Use only a device specifically rated for 600Y/347 V. Check conductor length and the required upstream overcurrent protection. | UL 1449; IEEE C62.41.1; IEEE C62.41.2 | Inspect all status windows and remote alarm contacts; verify that no phase module shows thermal failure. | Every 6–12 months |
| 6 | Compact Type 2, 3P, 230/400 V | TN-C or delta-compatible three-phase systems; no neutral module | Type 2; three-pole MOV configuration | 275 V L-PE or 440 V L-L, depending on wiring mode | 20 kA | 40 kA | ≤ 1.5 kV | 25 kA typical, subject to the upstream protective device | Compact distribution board; DIN rail | Use only where the earthing and neutral arrangement matches the wiring diagram. Add a neutral-to-earth module when required by the system configuration. | IEC 61643-11; IEC 60364-5-534 | Check the visual indicator and confirm correct phase and PE connections during isolation procedures. | Every 12 months |
| 7 | High-Capacity Type 2, 3P+N, 230/400 V | Commercial and light-industrial TN-S or TT systems | Type 2; replaceable plug-in modules | 275 V L-N; 255 V may be used for specific voltage tolerances | 30 kA | 60 kA | ≤ 1.8 kV | 25 kA to 50 kA, according to the tested backup protection | Main distribution board with accessible module replacement | Coordinate with a downstream Type 3 SPD by maintaining the specified cable distance or installing a decoupling inductor. | IEC 61643-11; IEC 60364-5-534 | Replace any module showing a red or failed indication. Inspect the base, wiring, and backup fuse before re-energizing. | Every 6 months |
| 8 | Low-Residual-Voltage Type 2, 3P+N | 230/400 V AC; sensitive commercial and control equipment | Type 2; low-Up coordinated MOV network | 275 V L-N | 15 kA | 30 kA | ≤ 1.2 kV | 25 kA minimum with specified backup protection | Distribution board close to sensitive loads | Use downstream of a higher-energy Type 1 or Type 2 protector. Keep connecting leads as short as possible, preferably below 0.5 m per conductor. | IEC 61643-11; IEC 60364-5-534; IEC 62305 where applicable | Check the indicator, remote alarm, PE conductor, and signs of overheating. Test after electrical events or equipment damage. | Every 6–12 months |
| 9 | Outdoor or Remote-Facility Type 1+2, 3P+N | 230/400 V AC; exposed sites, agricultural buildings, telecom shelters | Combined Type 1+2; high impulse-current capability | 275 V L-N | 12.5 kA per pole, 10/350 µs | 50 kA, 8/20 µs | ≤ 2.0 kV | 25 kA to 50 kA, based on the upstream protective arrangement | Incoming panel, preferably inside a weather-protected enclosure | Bond the SPD directly to the main equipotential bonding bar. Coordinate with surge protection on data, control, photovoltaic, and antenna cables. | IEC 61643-11; IEC 62305; IEC 60364-5-534 | Inspect enclosure seals, corrosion, indicators, bonding conductors, and remote alarm wiring after severe weather. | Before and after storm season |
| 10 | Type 2+3 Point-of-Use, 3P+N | 230/400 V AC; final distribution and sensitive equipment circuits | Type 2+3 coordinated protection | 275 V L-N | 5 kA to 10 kA | 10 kA to 20 kA | ≤ 1.0 kV | Usually coordinated with upstream overcurrent protection rather than used as a service-entrance device | Final distribution board or equipment panel | Never use as the only protector for a building. Install downstream of a suitable Type 1 or Type 2 device with the required coordination distance. | IEC 61643-11; IEC 60364-5-534; relevant national installation standards | Check status indicators and replace the unit after a confirmed surge, thermal disconnection, or failed insulation assessment. | Every 12 months |